Product overview
MTL4514_B 1channel DI relay output + LFD alarm made in England
MTL4514_B 1channel DI relay output + LFD alarm made in England
MTL4514_B product specification as below
MTL4514_B 1channel DI relay output + LFD alarm made in England
MTL4514/B –
MTL5514 SWITCH/ PROXIMITY DETECTOR INTERFACE 1-channel, line fault detection,
phase reversal The MTLx514 enables a safe–area load to be controlled, through a
relay, by a proximity detector or switch located in a hazardous area. Line
faults are signalled through a separate relay and indicated on the top of the
module. Switches are provided to select phase reversal and to enable the line
fault detection.
MTL4514_B 1channel DI relay output + LFD alarm made in England
SPECIFICATION
See also common
specification
Number of
channels
One
Location of
switch
Zone 0, IIC, T6
hazardous area
Div.1, Group A,
hazardous location
Location of
proximity detector
Zone 0, IIC,
T4–6 hazardous area, if suitably certified
Div.1, Group A,
hazardous location
Hazardous–area
inputs
Inputs
conforming to BS EN60947–5–6:2001 standards for
proximity
detectors (NAMUR)
Voltage applied
to sensor
7 to 9V dc from
1kΩ ±10%
Input/output
characteristics
Normal phase
Outputs closed
if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if
input < 1.2mA (> 10kΩ in input circuit)
Hysteresis:
200µA (650Ω) nominal
Line fault
detection (LFD) (when selected)
User-selectable
via switches on the side of the unit. Line faults
are indicated
by an LED. Line fault relay is energised and channel
output relay
de-energised if input line-fault detected
Open-circuit
alarm on if Iin < 50µA
Open-circuit
alarm off if Iin > 250µA
Short-circuit
alarm on if Rin < 100Ω
Short-circuit
alarm off if Rin > 360Ω
Note: Resistors
must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in
series with switch
20kΩ to 25kΩ in
parallel with switch
Safe-area
output
MTL4514 &
MTL5514
Channel: Single
pole relay with changeover contacts
LFD: Single
pole relay with changeover contacts
MTL4514B
Channel: Single
pole relay
LFD: Single
pole relay
Note: reactive
loads must be adequately suppressed
LED indicators
Green: power
indication
Yellow: channel
status, on when output energised
Red: LFD
indication, on when line fault detected
Maximum current
consumption
25mA at 24V dc
Power dissipation
within unit
0.6W at 24V
Safety
description
Uo=10.5V
Io=14mA Po=37mW Um = 253V rms or dc
MTL4514_B 1channel DI relay output + LFD alarm made in England
Other related models for MTL4500 series as below for your reference.
MTL4501-SR
MTL4504
MTL4510
MTL4510B
MTL4511
MTL4513
MTL4514D
MTL4514_B
MTL4516
MTL4516C
MTL4517
MTL4521
MTL4521L
MTL4523
MTL4523L
MTL4523R
MTL4523V-VL
MTL4524
MTL4524S
MTL4525
MTL4526
MTL4541
MTL4541A
MTL4541AS
MTL4541B
MTL4541P
MTL4541S
MTL4541T
MTL4544
MTL4544A
MTL4544AS
MTL4544B
MTL4544D
MTL4544S
MTL4546
MTL4546C
MTL4546S
MTL4546Y
MTL4549
MTL4549C
MTL4549Y
MTL4573
MTL4575
MTL4576-RTD
MTL4576-THC
MTL4581
MTL4582B
MTL4531
MTL4532
MTL4561
MTL4599
MTL4599N
MTL4514_B 1channel DI relay output + LFD alarm made in England
If you have any other question about MTL4514_B, please feel free to contact me here!
Contact details
HONGKONG XIEYUAN TECH CO., LIMITED
Telephone:86-
Mobile :86-(Whatapp&Wechat
is available)
Skype:xyautomation
E-mail:sales1@hkxytech.com
Leave a message for product
- 温馨提示:为规避购买风险,建议您在购买前务必确认供应商资质与产品质量。
- 免责申明:以上内容为注册会员自行发布,若信息的真实性、合法性存在争议,平台将会监督协助处理,欢迎举报