MTL5532 PULSE ISOLATO MTL 5532 PULSE ISOLATO
MTL5532 PULSE ISOLATO MTL 5532 PULSE ISOLATO
The MTLx532 isolates pulses from a switch, proximity detector, current
pulse transmitter or voltage pulse transmitter located in a hazardous
area. It is ideal for applications involving high pulse rates and fast
response times, by repeating the pulses into the safe area. An analogue
output proportional to frequency is also provided, together with a relay
output, which may be configured to act as an alarm. Configuration is
carried out with a personal computer.
SPECIFICATION
See also common specification
Number of channels
One, fully floating
Sensor type
MTL5532 PULSE ISOLATO MTL 5532 PULSE ISOLATO
Switch or proximity detector (NAMUR/BS EN 60947–5–6:2001)
2– or 3–wire voltage or pulse transmitter
Location of switch
Zone 0, IIC, T6 hazardous area
Div. 1, Group A, hazardous location
Location of proximity detector or transmitter
Zone 0, IIC, T4–T6 if suitably certified
Div.1, Group A, hazardous location
Input
Switch input:
Output ON if switch is closed
Proximity detector input:
Excitation: 7.0 to 9.0V dc from 1kΩ nominal
Output ON if input > 2.1mA* (< 2kΩ)
Output OFF if input < 1.2mA* (> 10kΩ)
Switching hysteresis: 0.2mA (650Ω) nominal
*NAMUR and BS EN 60947–5–6:2001standards
Current pulse input:
Transmitter supply: 16.5V dc at 20mA
Short circuit current: 24mA
MTL5532 PULSE ISOLATO MTL 5532 PULSE ISOLATO
Output: Iin > 9.0mA = ON, Iin < 7.0mA = OFF
Switching hysteresis: 0.5mA
Voltage pulse input
Input impedance: > 10kΩ
Switching point voltage (Vsp): 3, 6, or 12V nominal
(User selectable by switches on the side of the module)
Output: Vin > Vsp = ON, Vin < Vsp = OFF
Switching hysteresis: 100mV + (0.1 x Vsp) typical
Safe-area pulse output
Maximum delay: 10µs
Maximum off–state voltage: 35V
Maximum off–state leakage current: 10µA
Maximum on–state resistance: 25Ω
Maximum on–state current: 50mA
Output OFF if supply fails
Note: LFD signal is Zener-diode protected against inductive loads
Safe-area current output
Input capture delay: 2 signal periods (5ms min.)
Signal range: 4 to 20mA
Under/over range: 0 to 22mA
Load resistance: 0 to 450Ω @20mA
Output resistance: >1MΩ
Ripple: < 50µA peak-to-peak
Accuracy: better than 20µA at 20°C
Temperature drift: < 1µA/°C
Risetime (10% - 90%, after step change): 60 ms
Alarm output
MTL5532 PULSE ISOLATO MTL 5532 PULSE ISOLATO
Relay ON in alarm, 0.5A @ 35Vdc max.
Pulse width
High: 10µs min
Low: 10µs min
Frequency range
0 – 50kHz - pulse output mode
0 – 10KHz - for analogue output
LED indicators
Green: power indication
Yellow: on when output circuit is on
Red: flashing when line fault or error
Power requirement
65mA at 24V dc
70mA at 20V dc
55mA at 35V dc
Power dissipation within unit
1.35W maximum at 24V
1.75W maximum at 35V
Safety description (Um = 253V rms or dc)
Terminals 2 to 1 and 6 to 1
Uo=10.5V Io=14mA Po=37mW
Terminals 4 to 3 and 1
Uo=28V Io=93mA Po=651mW
Terminals 3 to 1
Non-energy-storing apparatus ≤1.5V, ≤0.1A and ≤25mW; can be
connected without further certification into any IS loop with an
open-circuit voltage <28V
Terminals 5 to 4 and 1
Vmax ≤ 28V, Imax ≤ 94mA, Pmax ≤ 0.66W
Configurator
A personal computer running MTL PCS45 software with a
PCL45USB serial interface.
MTL5532 PULSE ISOLATO MTL 5532 PULSE ISOLATO
MTL5501-SR FAIL-SAFE SWITCH/PROXIMITY DETECTOR INTERFACE WITH LFD
MTL5510 SWITCH/ PROXIMITY DETECTOR INTERFACE 4-CHANNEL, DIGITAL INPUT
MTL5510B SWITCH/ PROXIMITY DETECTOR INTERFACE 4-CHANNEL, MULTI-FUNCTION, DIGITAL INPUT
MTL5511 SWITCH/ PROXIMITY DETECTOR INTERFACE 1-CHANNEL, WITH LINE FAULT DETECTION
MTL5513 SWITCH/ PROXIMITY DETECTOR INTERFACE 2-CHANNEL, LINE FAULT DETECTION, PHASE REVERSAL
MTL5514 SWITCH/ PROXIMITY DETECTOR INTERFACE 1-CHANNEL, LINE FAULT DETECTION, PHASE REVERSAL
MTL5514D SWITCH/ PROXIMITY DETECTOR INTERFACE 1-CHANNEL, DUAL OUTPUT, LFD, PHASE REVERSAL
MTL5516C SWITCH/ PROXIMITY DETECTOR INTERFACE 2-CHANNEL, WITH LINE FAULT DETECTION
MTL5517 SWITCH/ PROXIMITY DETECTOR INTERFACE 2-CHANNEL, LINE FAULT DETECTION, PHASE REVERSAL
MTL5521 SOLENOID/ ALARM DRIVER LOOP-POWERED, IIC
MTL5522 SOLENOID/ALARM DRIVER LOOP-POWERED, IIB
MTL5523 SOLENOID/ALARM DRIVER WITH LINE FAULT DETECTION, IIC
MTL5523V - VL SOLENOID/ALARM DRIVER WITH LINE FAULT DETECTION, IIC
MTL5524 SOLENOID/ALARM DRIVER SWITCH OPERATED WITH OVERRIDE, IIC
MTL5525 SOLENOID/ALARM DRIVER SWITCH OPERATED WITH OVERRIDE, IIC, LOW POWER
MTL5526 SWITCH-OPERATED RELAY 2–CHANNEL IS–OUTPUT
MTL5541 REPEATER POWER SUPPLY 4/20MA, HART
, 2- OR 3-WIRE TRANSMITTERS
MTL5541A CURRENT REPEATER 4/20MA PASSIVE I/P FOR HART
TRANSMITTERS
MTL5541AS CURRENT REPEATER 4/20MA PASSIVE I/P FOR HART
TRANSMITTERS
MTL5541S REPEATER POWER SUPPLY 4/20MA, HART
, 2- OR 3-WIRE TRANSMITTERS
MTL5544 REPEATER POWER SUPPLY 2-CHANNEL, 4/20MA, HART
, 2- OR 3- WIRE TRANSMITTERS
MTL5544A CURRENT REPEATER 4/20MA PASSIVE I/P FOR HART
TRANSMITTERS
MTL5544AS CURRENT REPEATER 4/20MA PASSIVE I/P FOR HART
TRANSMITTERS
MTL5544D REPEATER POWER SUPPLY SINGLE CHANNEL, 4/20MA, HART
FOR 2- OR 3-WIRE TRANSMITTERS, TWO OUTPUTS
MTL5544S REPEATER POWER SUPPLY 2-CHANNEL, 4/20MA, HART
, 2- OR 3- WIRE TRANSMITTERS
MTL5546 ISOLATING DRIVER FOR 4–20MA HART
VALVE POSITIONERS WITH LINE FAULT DETECTION
MTL5546Y ISOLATING DRIVER FOR 4–20MA HART
VALVE POSITIONERS WITH LINE FAULT DETECTION
MTL5549 ISOLATING DRIVER TWO-CHANNEL, FOR 4–20MA, HART
VALVE POSITIONERS WITH LINE FAULT DETECTION
MTL5549Y ISOLATING DRIVER TWO-CHANNEL, FOR 4–20MA, HART
VALVE POSITIONERS WITH LINE FAULT DETECTION
MTL5575 TEMPERATURE CONVERTER THC OR RTD INPUT + ALARM
MTL5576-RTD TEMPERATURE CONVERTER RTD/POTENTIOMETER INPUT, 2-CHANNEL
MTL5576-THC TEMPERATURE CONVERTER MV/THC INPUT, 2-CHANNEL
MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR FOR LOW-LEVEL SIGNALS
MTL5582 RESISTANCE ISOLATOR TO REPEAT RTD SIGNALS
MTL5531 VIBRATION TRANSDUCER INTERFACE
MTL5532 PULSE ISOLATOR PULSE & 4/20MA CURRENT OUTPUTS
MTL5533 VIBRATION TRANSDUCER INTERFACE 2-CHANNEL
MTL5561 FIRE AND SMOKE DETECTOR INTERFACE 2-CHANNEL
MPA5500 A.C. POWER ADAPTOR
MTL5599 DUMMY ISOLATOR
MTL5991 24V DC POWER SUPPLY
MTL5599 DUMMY ISOLATOR MTL 5599 DUMMY ISOLATOR
Leave a message for product
- 温馨提示:为规避购买风险,建议您在购买前务必确认供应商资质与产品质量。
- 免责申明:以上内容为注册会员自行发布,若信息的真实性、合法性存在争议,平台将会监督协助处理,欢迎举报